14 Chromalox 3901 User’s Manual
Calibration
Procedure
(continued)
3. Set the sensor simulator to a maximum (900°F for
J T/C, 1600°F for K T/C). While pressing the
“READ TEMP” pushbutton, adjust the span
potentiometer until the digital display equals the
sensor input value (900°F or 1600°F).
4. Repeat steps 2 and 3 as many times as necessary
until both displays equal their respective sensor input
values.
5. Calibration complete.